FCS Multi Channel System Controllers

  • Available in 4 channels, 8 channels, 32 channels and 128 channels
  • FCS-M models offer Modbus® RTU RS-485 digital output signal for LAN and WAN communications
  • FCS-B models offer BACnet® MS/TP RS-485 output signal for WAN communications (for communicating with a BAS)
  • Graphic, full colour, touchpad LCD screen with LED indicators
  • Intuitive menu system with password protection
  • Optional internal analog inputs and/or analog outputs with flexible configuration settings
  • Enhanced logic control, zoning and priority structure capabilities
  • Supports 4-20 mA and Modbus® driven VFDs
  • 4 dry contact relays, 5A @ 240V each
  • 2 dedicated horn/strobe output drives, 0.5A @ 24VDC max
  • Line Voltage (90 – 240 VAC)
  • USB port for firmware upgrades and data logging
  • Configurable to comply with California Title-24 Energy Efficiency Standards
  • Door mounted audible alarm, optional water tight version available
  • Standard water / dust tight, corrosion resistant enclosure (drip proof); IP54 rated with water tight, door mounted audible alarm installed

Enclosure:  ABS / Polycarbonate, copper coated interior to reduce RF interference 

IP54 rating with door mounted, water tight buzzer installed

Size:  254 x 226 x 113 mm / 10.0 x 8.9 x 4.44 in

Display:  8.1 cm (3.2”) graphic, 1/4 VGA full colour resistive touch LCD screen with LED indicators for “POWER”, “STATUS 1, 2 and 3” and “FAULT”

Input:  Modbus® RTU RS-485 input 

4-20 mA analog input (optional)

Output:  Modbus® RTU RS-485 output to networked devices 

Modbus® RTU RS-485 output to BAS or DDC (FCS-M models) 

BACnet MS/TP RS-485 output to BAS or DDC (FCS-B models) 

2 outputs drives for strobe/horn, 0.5 A @ 24 VDC max 

Field configurable 4-20 mA or 0-10 volts analog output (optional)

Audible Alarm:  Standard loud, door mounted buzzer, 90 dB @ 30 cm (1 ft) 

Optional: door mounted, water tight buzzer, 85 dB @ 60.96 cm (2 ft)

Top Mounted Strobe:  Optional: bright, red, top mounted strobe, 10 – 30 VDC, 13 cm H x 6.1 cm dia / 5.2 inches H x 2.4 inches dia

Power Requirement:  Line Voltage: 90 – 240 VAC, 50 -60 Hz, 75 W

Power Distribution:  Total power available for Remote & Peripheral Devices and Options 65 W @ 24 VDC

Operating Temperature:  -20°C to 40°C (-4°F to 104°F)

with internal heater

-40°C to -40°C (-40°F to 104°F)

Conforms to:  CSA-C22.2 No. 205-12, UL508 (Edition 17):2007 

EMC Directive 2004/108/EC, EN 50270:2006, Type 1, EN61010 

FCC. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. 

FCS-B, FCS-B-X models are Listed by BTL (where X represents one or more factory installed Options) 

RoHS compliant circuit boards

  • Enclosed Parking Facilities
  • Recreation Facilities
  • Food Processing Plants
  • Cold Storage / Freezer Rooms
  • Refrigeration Plants
  • Chemical Storage Rooms
  • and many more…